Mount the module in high vibration areas, Wire the module, I/o connectors – Rockwell Automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input/Output User Manual

Page 18

Advertising
background image

10

Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012

Chapter 2 Install Your ArmorBlock Module

Mount the Module in High Vibration Areas

If you mount the module in an area that is subject to shock or vibration, we
recommend you use a flat and a lock washer to mount the module. Mount the flat
and the lock washer as shown in the mounting illustration. Torque the mounting
screws to 0.68 Nm (6 lb-in.).

High Vibration Area Mounting

Wire the Module

The 1732E-IF4M12R, 1732E-OF4M12R ArmorBlock EtherNet/IP modules
have 5-pin micro-style M12 I/O connectors. We provide caps to cover the unused
connectors on your module. Connect the quick-disconnect cord sets you selected
for your module to the appropriate ports.

I/O Connectors

(1)

Micro-style M12 5-Pin Input Female Connector – 1732E-IF4M12R

Micro-style M12 5-Pin Input Female Connector – 1732E-OF4M12R

45768

Lock washer

Flat washer

(1) Only 4 of the 5 pins are active. The center pin (5) is internally tied to signal ground to minimize

external noise pickup.

3

4

1

2

5

45868

(View into connector)
Pin 1 Current Input +
Pin 2 Current Common
Pin 3 Voltage Input +
Pin 4 Voltage Common
Pin 5 No Connect

3

4

1

2

5

45868

(View into connector)
Pin 1Current Output +
Pin 2Current Common
Pin 3Voltage Output +
Pin 4Voltage Common
Pin 5No Connect