Configure your i/o module, Rslogix 5000 configuration software – Rockwell Automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input/Output User Manual

Page 24

Advertising
background image

16

Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012

Chapter 3 Configure Your Analog Input and Output Modules with RSLogix 5000 Software

Configure Your I/O Module

You must configure your module upon installation. The module will not work
until it has been configured with at least the default configuration.

RSLogix 5000 Configuration Software

You must use RSLogix 5000, version 20 or later, to configure your module. You
have the option of accepting default configuration for your module or writing
point-level configuration specific to your application.

Both options are explained in detail, including views of software screens, in this
chapter.

Overview of the
Configuration Process
through RSLogix 5000

When you use the RSLogix 5000 software to configure a module, you must
perform the following steps:

1.

Add the Local EtherNet/IP Bridge (1756-EN2T, 1756-EN2TR, or
1756-EN3TR) to your project’s I/O Configuration.

2.

Add the 1732E-IF4M12R or 1732E-OF4M12R module as a child of the
1756-EN2T module.

3.

Accept the default configuration or change it to specific configuration for
the module.

4.

Edit configuration for a module when changes are needed.

Add a New Bridge and
Module to Your
RSLogix 5000 Project

After you have started RSLogix 5000 software and created a controller, you must
add a new bridge and a new module to your project. The bridge allows your
module to communicate with the controller.

The wizard allows you to create a new module and write configuration. You can
use default configuration or write specific configuration for your application.

IMPORTANT

Click Help on the configuration dialogs shown in this section if you
need assistance in selecting and setting the parameters.