Chapter 5 Calibrate Your Modules

12.

Click Next to calibrate the module.
The Output Calibration Results page appears.

• For failed calibration, go to step

13

.

• For successful calibration, go to step

14

.

13.

If the calibration failed, click Retry to recalibrate the same channel.
This takes you back to steps

8

12

until you get successful calibration on

the channel.

14.

If the calibration is successful, click Next to start calibration on the next
channel (in this example, channel 1).
This takes you back to steps

8

12

. You will have to go through the same

steps for each of the next channels lined up for calibration.

15.

After successful calibration on the channel(s), click Finish to close the
Calibration Wizard.

Chapter Summary

This chapter provided a step-by-step guide on how to calibrate your ArmorBlock
analog input and output modules.