Rockwell Automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input/Output User Manual

Page 63

Advertising
background image

Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012

55

Calibrate Your Modules Chapter 5

While you are online, you must access the Calibration tab on the Module
Properties dialog box through RSLogix 5000.

Follow these steps to calibrate your module.

1.

Click Calibration Tab on the Module Properties dialog box.

2.

Check the Calibrate checkbox to specify which channel to calibrate.
In this example, check Channels 0…3.

3.

Under Calibrate Channels select One At a Time.

4.

Click Start Calibration. This button is active when:
• the system is online, and
• you selected at least one of the channels.

Note that you can press the F1 button on your keyboard or click Help from
the wizard and warning message that appear to get detailed information
about the procedures for calibration.

5.

After clicking Start Calibration, a warning dialog appears notifying you of
the risk involved in calibrating an active system and gives you the option to
quit.

Choose whether to calibrate each

channel one at a time or in groups all

at once