Chapter 4 Configurable Features for the Analog Input and Output Modules

outside that range. This safety feature sets a high clamp and a low clamp. Once
clamps are determined for a module, any data received from the controller that
exceeds those clamps sets an appropriate limit alarm and transitions the output to
that limit but not beyond the requested value.

For example, an application may set the high clamp on a module for 8V and the
low clamp for -8V. If a controller sends a value corresponding to 9V to the
module, the module will only apply 8V to its screw terminals.

Clamping alarms can be disabled or latched on a per channel basis.

To set clamping limits via RSLogix 5000, go to

page 36

.

Clamp/Limit Alarms

This function works directly with clamping. When a module receives a data value
from the controller that exceeds clamping limits, it applies signal values to the
clamping limit but also sends a status bit to the controller notifying it that the
value sent exceeds the clamping limits.

Using the example above, if a module has clamping limits of 8V and -8V but then
receives data to apply 9V, only 8V is applied to the screw terminals and the
module sends a status bit back to the controller informing it that the 9V value
exceeds the module’s clamping limits.

To set clamping alarms via RSLogix 5000, go to

page 36

.

Data Tables

The data structure of each Assembly instance used by the Analog Input and
Output modules is defined in the tables below.

1732E-IF4M12R – Configuration Assembly Instance 100 Data Structure

Configuration
Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

4…5

Channel 0 Low Engineering

6…7

Channel 0 High Engineering

8…9

Channel 0 Digital Filter

10…11

Channel 0 Low Alarm

12…13

Channel 0 High Alarm

14…15

Channel 0 Low Low Alarm

16…17

Channel 0 High High Alarm

18

Channel 0 Input Range

19

Channel 0 Enable Alarm Latch

20

Channel 0 Disable Alarms

21…23

Reserved (Ignore)

24…25

Channel 1 Low Engineering