Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012

Chapter 2 Install Your ArmorBlock Module

Both modules require two 24V DC (nominal) supplies. These supplies are called
the Module Power and the Auxiliary Power. The Module power supplies the
microprocessor and Ethernet portions of the module. The Auxiliary Power
provides power for the voltage or current outputs on the 1732E-OF4M12R
analog output module.

Internally, the Module Power and Auxiliary Power are electrically isolated.

Chapter Summary

In this chapter, you learned how to install and wire your module. The following
chapter describes how to configure your module to communicate on the
EtherNet/IP network by providing an IP address, gateway address, and Subnet
mask.

IMPORTANT

The maximum current that any pin on the power connectors can
carry is 4 A.

ATTENTION: To comply with the CE Low Voltage Directive (LVD), this
equipment and all connected I/O must be powered from a source
compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

ATTENTION: To comply with UL restrictions, this equipment must be
powered from a source compliant with the following: Limited Voltage/
Limited Current.

ATTENTION: The device meets UL Type 1 Enclosure rating.