Calibrate Your Modules Chapter 5

7.

After clicking Start Calibration, a warning dialog appears notifying you of
the risk involved in calibrating an active system and gives you the option to
quit.

If at least one channel has been selected and there is a mismatch between
the device in the RSLogix 5000 I/O Configuration and the actual physical
device, another warning dialog comes up. It informs you that this is
dangerous with an active system and there is a mismatch. This message box
gives you an option to quit. Help is provided to you more information.

8.

From the Danger dialog, for a module not currently used for control, click
OK to continue.
The Output Calibration - Low Value dialog appears.

9.

Record the results of your measurement.

10.

Click Next. The Output Calibration - High Value dialog appears.

11.

Record the results of your measurement.