61

Calibrate Your Modules Chapter 5

• For failed calibration, go to step

13

.

• For successful calibration, go to step

14

.

13.

If the calibration failed, click Retry to recalibrate the same channel.
This takes you back to steps

8

12

until you get successful calibration on

the channel.

14.

If the calibration is successful, click Next to start calibration on the next
channel (in this example, channel 1).
This takes you back to steps

8

12

. You will have to go through the same

steps for each of the next channels lined up for calibration.

15.

After successful calibration on the channel(s), click Finish to close the
Calibration Wizard.

Voltage Meter Calibrations

RSLogix 5000 software commands the module to output specific levels of
voltage. You must measure the actual level and record the results. This
measurement allows the module to account for any inaccuracies.

While you are online, you must access the Module Properties dialog box. See

Edit

Your 1732E-OF4M12R Configuration on page 30

.

Follow these steps to calibrate your module.

1.

Connect your voltage meter to the module.

2.

Go to the Configuration tab on the Module Properties dialog box.