background image

22

Rockwell Automation Publication 6180P-UM001C-EN-P - February 2014

Chapter 2

Installation

Required Tools

These tools are required for computer installation:

#2 cross-head screwdriver
Panel cutout tools
Antistatic wrist strap

Install the Computer

You can install these computers in a panel by using mounting clips. Computers
are mounted through a rectangular cutout in the panel.

Panel Mounting Guidelines

Observe these guidelines when installing the computer in a panel:

Remove all electrical power from the panel before making the cutout.
Confirm that there is adequate space behind the panel. For specific

information, refer to

Mounting Clearance Requirements

on

page 20.

Cut supporting panels to specifications before installation. Take precautions

so metal cuttings do not enter components already installed in panel.

Supporting panels must be at least 14 gauge for proper sealing against water
and dust and to provide proper support. The mounting hardware supplied
accommodates panel thickness between 1.5…5.5 mm (0.06…0.22 in.).

Make sure the area around the panel cutout is clear.

Panel Cutout Dimensions

The computers must be mounted to meet the panel cutout dimensions specified
below.

ATTENTION: Failure to follow these guidelines can result in personal
injury or damage to the panel components.

Model

Cutout Dimensions (HxW), approx

1200P

279.0 x 450.0 mm (10.98 x 17.72 in.)

1500P

326.4 x 429.3 mm (12.85 x 16.90 in.)