Converter Parameters

B-3

Parameter List for MDI Drives

No.

Name and Description

Details

01

Adapter Cfg
Sets the operation of the converter on
MDI. Leave at “Auto” (setting) when used
with software tools.

Important: Adapter Cfg (01) must be set
to “Auto” (default) for V*S Utilites to
operate. HyperTerminal can be used if this
parameter needs to be changed (see
Using Terminal Evaluation Software on
page 4-11).

Default:

0 = Auto

Values:

0 = Auto
1 = Master
2 = Slave
3 = RTU Master
4 = RTU Passthru

Type:

Read/Write

Reset Required:Yes

02

Reset Module
No action if set to “Ready.” Resets the
converter if set to “Reset Module.”
Restores the converter to its
factory-default settings if set to “Set
Defaults.” This parameter is a command. It
will be reset to “0 = Ready” after the
command has been performed.

Default:

0 = Ready

Values:

0 = Ready
1 = Reset Module
2 = Set Defaults

Type:

Read/Write

Reset Required:No

03

Clear DF1 Counts
No action if set to “Ready.” Resets the
DF1 statistical parameter DF1 Packets
Sent (04)
and DF1 Packets Rcvd (05) to
0 if set to “Clear Counts.” This parameter
is a command. It will be reset to “0 =
Ready” after the command has been
performed.

Default:

0 = Ready

Values:

0 = Ready
1 = Clear Counts

Type:

Read/Write

Reset Required: No

04

DF1 Packets Sent
Displays the number of DF1 packets sent
by the converter. The value of this
parameter is normally approximately
equal to the value of DF1 Packets Rcvd
(05)
.

Default:

0

Minimum: 0

Maximum: 65535

Type:

Read Only

!

ATTENTION: Risk of injury or equipment damage exists. If
the converter is transmitting I/O that controls the drive
(indicated by a solid green diamond LED), the drive may fault
when you remove or reset the converter. Determine how your
drive will respond before removing or resetting a connected
converter.