USB Converter User Manual

Setting Drive Addresses

1.

For Drive 1 connected to the 1203-USB converter, set drive parameter Comm
Node Addr (104) to match the converter node address (default = 1) set with drive
parameter RTU DSI Addr Cfg (06).

Important: When setting the 1203-USB converter node address, do not use a value

higher than “77” octal.

2.

For each remaining drive to be networked, set drive parameter Comm Node Addr
(104) to a unique address.

Setting Comm Loss Action

For each drive to be networked (including Drive 1 connected to the 1203-USB
converter), set drive parameter Comm Loss Action (105) to either “1” (Coast to Stop)
or “2” (Stop).

Power Cycle All Drives

Power cycle each drive so that all new settings established in this section will take
effect.