Flash Updates

C-9

Troubleshooting HyperTerminal Flash Problems

Description

Corrective Action

The “Transfer Cancelled by Remote
System” message appears and the flash
is not completed.

Restart HyperTerminal and repeat
the flash procedure.

If you are using Windows NT 4.0,
install SP3 or later. Windows NT
service packs are available from the
Microsoft web site:

http://www.microsoft.com.

Download a HyperTerminal Private
Edition update from the Hilgraeve
web site:

http://www.hilgraeve.com.

(Please note that there is a license
requirement with this software.)
Then, perform the flash procedure
again.

The “Xmodem File Send” for dialog box
appears, but the flash file is not
transferred.

Verify that you have selected the
Xmodem protocol in the Send File
screen.

Verify that the new file is on your
computer hard drive. Do not attempt
to flash from a removable storage
device or a network.

Verify that you are sending the file
within 60 seconds of pressing “Y” to
confirm that you want to perform the
flash.

After completing a flash, you are unable to
communicate with the converter. For
example, meaningless text appears on the
HyperTerminal screen.

Verify that the software tool’s virtual
COM port rate is set to 115200. If
parameters are changed during a
flash update, all parameters are set to
their default settings.

You are unable to initiate a flash to a DPI
host or peripheral product.

DPI Drives: Verify that converter
parameter Interface Mode (06) is
set to “Auto” (default setting).

MDI Drives: Verify that converter
parameter Adapter Cfg (01) is set
to “Auto.”