8 digital input menu, Digital input menu – Rice Lake 420 Plus HMI Digital Weight Indicator Installation Manual User Manual

Page 31

Advertising
background image

420 Plus Installation Manual - Configuration

27

3.2.8

Digital Input Menu

XXXXXXX

XXXXXXX

XXXXXXX

XXXXXXX

DIGIN1

OFF

DIGIN2

ZERO

T ARE

NT/GRS

UNITS

DSPTAR

PRINT

CLRCN

OFF

ZERO

T ARE

NT/GRS

UNITS

DSPTAR

PRINT

CLRCN

ALGOUT

DIGI N

SETPNT

PROGRM PFORMT

SERIAL

CALIBR

CONFIG FORMAT

HOLD

HOLD

KBDLOC KBDLOC

VERS

CLRTAR

CLRTAR

CLRACC

CLRACC

ACCUM

NEWID

ACCUM

NEWID

Figure 3-12. Digital Input Menu

Table 3-8. Digital Input Menu Parameters

DIG IN Menu

Parameter

Choices

Description

Level 2 submenus

DIGIN1
DIGIN2

OFF
ZERO
TARE
NT/GRS
UNITS
DSPTAR
PRINT
CLRCN
KBDLOC
HOLD
CLRTAR
ACCUM
CLRACC
NEWID

Specifies the function activated by digital inputs 1 and 2.

• ZERO, NT/GRS (net/gross mode toggle), TARE, UNITS, and PRINT provide the same

functions as the front panel keys.

• DSPTAR displays the current tare value.
• CLRCN resets the consecutive number to the value specified on the CONSTU parameter

(PROGRM menu).

• KBDLOC disables the keypad while the digital input is held low.
• HOLD holds the current display. Releasing this input clears the running average filter.
• CLRTAR clears the tare.
• ACCUM displays the accumulator.
• CLRACC clears the accumulator.
• NEWID enters the ID number.

Advertising