Reporting Commands

Reporting commands send specific information to the
serial port. The commands listed in Table 6-5 can be
used in all modes.

Transmitting all configuration settings can be
achieved by the DUMPALL command or by
pressing PRINT while in menu mode.

6.1.6

Clear and Reset Commands

The following commands can be used to clear and
reset the

Counterpart

:

RS

: Reset system. Resets the indicator without

resetting the configuration.

RESETCONFIGURATION

: Restores all

configuration parameters to their default values
(menu mode only). The

RESETCONFIGURATION

function can also be initiated by pre ssing
navigating to the

DEFALT

parameter under the

VERS menu and selecting YES. Then press

ENTER

to reset the indicator.

All load cell calibration settings are lost
w h e n t h e R E S E T C O N F I G U R AT I O N
command is run.

CLEARBUFFER

: Clears the buffer information.

6.1.7

Parameter Setting Commands

Parameter setting commands allow you to display or
change the current value for a particular configuration
parameter (Tables 6-6 through 6-12).

Current configuration parameter settings can be
displayed in all modes using the following syntax:

command<ENTER>

Most parameter values can be changed in menu mode
only.

Use the following command syntax when changing
parameter values:

command=value<ENTER>

, where

value

is either a number or a parameter value. Use no spaces
before or after the equal (=) sign. If you type an
incorrect command, the display reads

??

.

For example, to set the motion band parameter to 5
divisions, type the following:

SC.MOTBAND=5<ENTER>

For parameters with selectable values, enter the
command and equal sign followed by a question
mark:

command=?<ENTER>

to see a list of those values.

The indicator must be in menu mode to use this
function.

Some parameters are valid only if other
parameters or parameter values are
specified. Restrictions for front-panel

configuration also apply to serial command configuration.

Command

Function

DUMPALL

List all parameter values and ID
information

DUMPCONFIG

List all parameter values excluding ID
information

DUMPAUDIT

List audit trail information

DUMPIDS

List all ID information

DUMPIDINDEX

List a specific ID by index. See table 6-13
for more information.

DUMPIDCODE

List a specific ID by code. See table 6-13
for more information.

VERSION

Write

Counterpart

software version

P

Write current displayed weight with units
identifier. See Section 9.2.1 on page 67.

XE

Returns a 10-digit code representing any
error conditions currently shown on the
front panel.