AquaSmart Boiler Control Manual

Figure 14 (continued) - 7600A/B alternate multi-zone connections

with or without a tankless coil

Control Wiring (Option 2): 7600A only

CAUTION - Always observe proper polarity when connecting multiple transformers in a

system (connect red terminal of external transformer to TR terminal of AquaSmart).

1. Set “DHWP OFF” (default, see programming section for instructions)
2. Set “C1 on TT” (default, see programming section for instructions)
3. Circulator-on delay will affect all zones. Circulator-off delay will have no effect.
4. 24 VAC zone valves cannot be powered directly with the 7600A. Add an additional transformer for

every two or less valves.

5. Ensure there are no jumpers between the terminals of the zone valves.

◄ CONTINUED FROM PREVIOUS PAGE

TR

TW

120 VAC

BURNER OR

GAS IGNITION

SYSTEM

SK10046

L2 L1 C1 C2 ZC ZR B1 B2

NEUTRAL

HOT

120 VAC

BLACK

WHITE

CIRCULATOR

120 VAC

GENERAL

CIRCULATOR

Y

TR

TH

R

R

Y

40 VA

TRANSFORMER

ZONE 1

LOW VOLTAGE

THERMOSTAT

ZONE 1

24 VAC

ZONE VALVE

ZONE 2

LOW VOLTAGE

THERMOSTAT

ZONE 3*

LOW VOLTAGE

THERMOSTAT

Taco

550

ZONE 2

24 VAC

ZONE VALVE

ZONE 3*

24 VAC

ZONE VALVE

Honeywell

V8043E, V8044E

Honeywell

V8043F

MTR

MTR

TH/

TR

3

2

1

MTR

FIELD/MFR.

SUPPLIED

SERVICE

SWITCH

40 VA

TRANSFORMER

* Additional zones can be added by duplicating the

plumbing and wiring of zone 3, adding additional

transformers as needed.