AquaSmart Boiler Control Manual

2-in-1 “Integrated Unit” Instructions

This is very important for successful control operation.

1. Remove the existing immersion well. Clean the

threads in the boiler port tapping. Follow all applicable

safety codes, rules and guidelines for removing/

installing immersion wells.

2. Apply pipe sealant to the 2-in-1 sensor threads and

install it securely into the port. BECKETT

RECOMMENDS ONLY TO USE TEFLON TAPE OR

RECTORSEAL NO. 5 PIPE SEALANT.

3. Tighten with 1-1/8” open end or box wrench (torque

requirement: 185 - 200 in./lbs.). Pipe wrenches,

pliers, and adjustable wrenches will damage/round-off

the hex.

4. Securely install the AquaSmart control to the sensor.

Plug the 2-in-1 Sensor RJ connector (phone jack style)

into the receptacle (Item

a, Figure 6a) on the control.

5. Route the 36” green wire through the AquaSmart

bottom rectangular slot (Item

c, Figure 6a). Securely

install the fork connector of the 36” ground wire and

the ground wire from the 2-in-1 sensor under the

ground screw at the bottom of the control (Item

b,

Figure 6a).

6. Thoroughly clean the pipe surface and securely

tighten the pipe clamp on the water inlet pipe to the

boiler as close to the boiler as possible.

7. Route the 36” green ground wire to the pipe clamp

then cut to proper length, if necessary.

8. Strip the wire and insert the stripped end into hole on

the pipe clamp (item

d, Figure 6b). Tighten retaining

screw against the wire making sure that you have

good contact.

9. Complete control wiring and fill the appliance with

water to the pressure required, according to appliance

manufacturer’s instructions. Make sure all air is

purged from the system and there are no leaks. Turn

on power to the appliance and observe one call for

heat cycle with shut off at set temperature.

2-in-1 “Replaceable Unit” Instructions

This is very important for successful control operation.

1. Remove the existing immersion well. Clean the

threads in the boiler port tapping. Follow all

applicable safety codes, rules and guidelines for

removing/installing immersion wells.

2. Apply pipe sealant to the 2-in-1 replaceable

thermowell threads and install it securely into the port.

BECKETT RECOMMENDS ONLY TO USE TEFLON

TAPE OR RECTORSEAL NO. 5 PIPE SEALANT.

3. Tighten with 1-1/8” open end or box wrench (torque

requirement: 185 - 200 in./lbs.). Pipe wrenches,

pliers, and adjustable wrenches will damage/round-off

the hex.

4. Insert the sensor probe into the thermowell and push

it completely in until the sensor bottoms out (see

Figure 7). Route the sensor leads through the control

opening (Item

h, Figure 6a) and securely install the

control to the thermowell.

5. Plug the 2-in-1 Sensor RJ connector (phone jack

style) into the receptacle (Item

a, Figure 6a) on the

control.

6. Route the 36” green wire through the AquaSmart

bottom rectangular slot (Item

c, Figure 6a). Securely

install the fork connector of the 36” ground wire and

the ground wire from the 2-in-1 sensor under the

ground screw at the bottom of the control (Item

b,

Figure 6a).

7. Thoroughly clean the pipe surface and securely

tighten the pipe clamp on the water inlet pipe to the

boiler as close to the boiler as possible.

8. Route the 36” green ground wire to the pipe clamp

then cut to proper length, if necessary.

9. Strip the wire and insert the stripped end into hole on

the pipe clamp (item

d, Figure 6b). Tighten retaining

screw against the wire making sure that you have

good contact.

10. Complete control wiring and fill the appliance with

water to the pressure required, according to appliance

manufacturer’s instructions. Make sure all air is

purged from the system and there are no leaks. Turn

on power to the appliance and observe one call for

heat cycle with shut off at set temperature.