AquaSmart Boiler Control Manual

◄ CONTINUED FROM PREVIOUS PAGE

Control Wiring (Option 2): 7600A only

CAUTION - Always observe proper polarity when connecting multiple transformers in a

system (connect red terminal of external transformer to TR terminal of AquaSmart).

1. Set “DHWP on ZR” (see programming section for instructions)
2. Set “C1 on BOTH” (see programming section for instructions)
3. Circulator-on delay will affect all zones. Circulator-off delay will have no effect.
4. 24 VAC zone valves cannot be powered directly

with the 7600A. Add an additional transformer as

shown for every two or less valves.

5. Ensure there are no jumpers between the

terminals of the zone valves.

TH/

TR

TR

TW

ZONE 1

LOW VOLTAGE

THERMOSTAT

ZONE 1

24 VAC

ZONE VALVE

SK10047

L2 L1 C1 C2 ZC ZR B1 B2

NEUTRAL

HOT

120 VAC

BLACK

WHITE

CIRCULATOR

120 VAC

GENERAL

CIRCULATOR

TR

TH

Honewell

V8043F

ZONE

RELAY

T

T

1/H

2/N

3

4

5

6

DHW ZONE

24 VAC

ZONE VALVE

Y

R

R

Y

ZONE 3*

LOW VOLTAGE

THERMOSTAT

ZONE 3*

24 VAC

ZONE VALVE
Honewell

V8043E, V8044E

Taco

550

ZONE 2

24 VAC

ZONE VALVE

ZONE 2

LOW VOLTAGE

THERMOSTAT

TH

TR

DHW

LIMIT

CONTROL

Honeywell

V8043F

MTR

TH/

TR

MTR

MTR

40 VA

TRANSFORMER

3

2

MTR

1

FIELD/MFR.

SUPPLIED

SERVICE

SWITCH

120 VAC

BURNER OR

GAS IGNITION

SYSTEM

40 VA

TRANSFORMER

Figure 17 (continued) - 7600A/B alternate multi-zone

connections with Indirect Domestic Hot Water (DHW)

* Additional zones can be added by duplicating the

plumbing and wiring of zone 3, adding additional

transformers as needed.