How a Boiler Control Works

Figure 19 - Cold Start Operation (Low Limit ► OFF)

Figure 20 - Warm Start Operation (Low Limit ► ON)

(To maintain domestic hot water temperature)

High Temperature Limit

(Adjustable 100° to 220°F)

Shuts burner off at HIGH LIMIT set point.

High Temperature Differential

(Adjustable 5° to 45°F)

Starts the burner when temperature drops to the

HIGH LIMIT DIFFERENTIAL setting.

Example Shown:
High Limit = 200°

Differential = 20°

During a call for heat, the burner will be

shut off at 200° and be turned back on at

180° (200°-20°). The circulator will

continue to operate until the call for heat

is satisfied.

Low Temperature Limit

(Adjustable 100° to 205°F)

Starts the burner at LOW LIMIT

set point.

Low Temperature Differential

(Adjustable 10° to 45°F)

Shuts burner off when temperature rises to

the LOW LIMIT DIFFERENTIAL setting.

High Temperature Limit

(Adjustable 100° to 220°F)

Shuts burner off at HIGH LIMIT set point.

High Temperature Differential

(Adjustable 5° to 45°F)

Starts the burner when temperature drops to the

HIGH LIMIT DIFFERENTIAL setting.

Example Shown:
Low Limit = 140°

Differential = 10°

During the OFF cycle with no call for

heat, the burner is turned on at 140° to

maintain the boiler water temperature

and is shut off at 150° (140°+10°).

Example Shown:
High Limit = 200°

Differential = 20°

During a call for heat, the burner will be

shut off at 200° and be turned back on at

180° (200°-20°). The circulator will

continue to operate until the call for heat

is satisfied.