Service final checklist accessories, 7600rmu, 7600tsu – Beckett 7600 AquaSmart Boiler Control User Manual

Page 34

Advertising
background image

34

During Annual Maintenance or More Frequent

Service Intervals, Verify the below items.

Note: The 7600 control has no serviceable internal

parts. DO NOT attempt to repair a malfunctioning

control.

The control is clean and all vents are free of dust, lint or

foreign material.

All wiring is tight, terminals are free from corrosion and

insulation is intact.

There is no physical damage to the case or display.

There is no evidence of water damage on the control or

terminals.

The control is securely mounted to the well or other

mounting support.

The sensor is in its place, with no evidence of tampering.

The sensor lead on remote mounted units is in good

condition and securely anchored in the immersion well

with the strain relief.

The control temperatures, differentials and optional

functions are set correctly and working to established

specifications. Consult the service tag or label on the

boiler.

A record of service and any adjustments are made to the

service label or tag.

The control door is attached and securely closed.

Before Leaving the Installation Site, Verify:

All wiring has been done correctly in a workmanlike way,

is secure and meets all applicable codes.

AquaSmart control temperature settings, differentials and

optional functions are correctly set.

The control program is functioning properly by observing

at least one complete cycle.

At shutdown, the temperature and pressure level match

the recommended settings.

The pressure relief valve operation and boiler water feed

system works properly by bleeding some water and

observing the refill cycle.

The low water cutoff operation by lowering the water level

until it shuts the burner off.

The boiler passages and vent system are clear of

obstructions and operating to the appliance

manufacturer’s specifications and all required clearance

dimensions to combustible materials are met.

With combustion test instruments the burner is set to

manufacturer’s specifications.

After the system has run through a complete cycle, that

all fittings are free of leaks.

A record has been made of all service work and all

temperature control settings and optional functions.

Attach a label or tag to the boiler for future reference.

The AquaSmart Installation Manual is left at a suitable

location near the boiler for future reference and the

equipment owner is informed of this.

The control door is attached and securely closed.

Service

Final Checklist

Accessories

7600RMU

AquaSmart Remote Mount Unit Pack

Includes:

Cable Assembly with Coupler

Mounting Template

Self-drilling Screws (Qty:3)

Cable Ty-wrap

7600TSU

AquaSmart Temperature Sensor Unit Pack

Includes:

Temperature Sensor

Cable Ty-wrap

Joint Compound

Installation Instructions

76002N1S01U

AquaSmart 2-in-1 Sensor Unit Pack

Includes:

2-in-1 Sensor

36” Ground Wire

Pipe Clamp for grounding

Installation Instructions

76002N1R03U

AquaSmart 2-in-1 Replaceable Sensor Unit Pack

Includes:

Thermowell

Sensor Probe

36” Ground Wire

Pipe Clamp for grounding

Installation Instructions

Advertising