Control wiring (option 3): utilizing a zone panel – Beckett 7600 AquaSmart Boiler Control User Manual

Page 22

Advertising
background image

22

Figure 16 (continued) - 7600A/B multi-zone connections

with Indirect Domestic Hot Water (DHW)

◄ CONTINUED FROM PREVIOUS PAGE

Control Wiring (Option 3): Utilizing a Zone Panel

1. Set “DHWP on TT” (see programming section for instructions).
2. Set “C1 on TT” (default, see programming section for instructions).
3. Circulator-on and -off delay will only effect DHW zone.
4. A call for heat on TT (from the DHW zone) will change boiler set point to the high limit. All

other zones willheat to the reset temperature determined by the HeatManager.

5. Ensure that the zone panel and AquaSmart are powered from the same service switch.

DHW

LIMIT

CONTROL

L2 L1 C1 C2 ZC ZR B1 B2

TR

TW

SK10036

ZONE

PANEL

NEUTRAL

HOT

120 VAC

BLACK

WHITE

X

X

L1
L2

Z1

Z2

Z3*

P2

CIRCULATOR

120 VAC

P3

CIRCULATOR

120 VAC

P4*

CIRCULATOR

120 VAC

ZONE 1

LOW

VOLTAGE

THERMOSTAT

ZONE 2

LOW

VOLTAGE

THERMOSTAT

ZONE 3*

LOW

VOLTAGE

THERMOSTAT

END

SWITCH

7600A:

120 VAC BURNER OR

GAS IGNITION SYSTEM

7600B:

24 VAC GAS

IGNITION SYSTEM

FIELD/MFR.

SUPPLIED

SERVICE

SWITCH

ZC

ZR

P1

CIRCULATOR

120 VAC

* Additional zones can be added by duplicating

the plumbing and wiring of zone 3.