To ensure smooth appliance operation, the AquaSmart

requires a separation between the High and Low limits

no less than the greater differential plus 5°F. For

example: If the HIGH LIMIT is set to 180°F, the HIGH

DIFF to 20°F, and the LOW DIFF to 10°F, the control will

not allow a LOW LIMIT above 155°F (180°F - 20°F [the

greater of the two differentials] - 5°F = 155°F).

A. Temperature High Limit

1. In any mode or screen other than an OPTION

sub-menu, press the

“HIGH LIMIT”

key.

2. The following screen will be displayed:

HIGH LIMIT: 180F

CHANGE AND ENTER

The temperature displayed is the current setting.

Use the

and

keys to select the desired setting.

Tap the button to increase or decrease the

temperature by 1°, or hold it to increase or

decrease the temperature by 5° at a time. The

control will not allow you to select out-of-range

values.

3. Press the

“ENTER (RESET)”

key.

4. The control will ask you to confirm the setting with

the following screen:

HIGH LIMIT: 160F

ENTER OR CANCEL

Press

“ENTER (RESET)”

if the value is correct, or

“CANCEL (BACK)”

if it is not.

B. Temperature Low Limit

1. In any mode or screen other than an OPTION

sub-menu, press the

“LOW LIMIT”

key.

2. The following screen will be displayed:

LOW LIMIT: 140F

CHANGE AND ENTER

The temperature displayed is the current setting.

Use the

“▲”

and

“▼”

keys to select the desired

setting. Tap the button to increase or decrease the

temperature by 1°, or hold it to increase or

decrease the temperature by 5° at a time. The

control will not allow you to select out-of-range

values. For cold-start operation, turn the low limit

off by pressing the down arrow key repeatedly until

OFF is displayed.

IMPORTANT: To prevent flue gas condensation

and reduce fatigue caused by thermal cycling on

conventional (non-condensing) boilers, the LOW

LIMIT set point should be 150° F or above.

NOTE: Appliance manufacturer’s temperature

requirements supersede this recommendation.

3. Press the

“ENTER (RESET)”

key.

4. The control will ask you to confirm the setting with

the following screen:

LOW LIMIT: 150F

ENTER OR CANCEL

Press

“ENTER (RESET)”

if the value is correct, or

“CANCEL (BACK)”

if it is not.

C. Temperature High Limit Differential

1. In any mode or screen other than an OPTION

sub-menu, press the

“HIGH DIFF”

key.

2. The following screen will be displayed:

HIGH DIFF: 10F

CHANGE AND ENTER

The temperature displayed is the current setting.

Use the

“▲”

and

“▼”

keys to select the desired

setting. Tap the button to increase or decrease the

temperature by 1°, or hold it to increase or

decrease the temperature by 5° at a time. The

control will not allow you to select out-of-range

values.

Programming Basic Functions

Figure 18 - AquaSmart Keypad

Electrical Shock Hazard.

Can cause severe injury, death, or

equipment damage.

Live line voltage wires and connections will be exposed

while programming the AquaSmart. Take care to touch

only the AquaSmart keypad while programming the control.

Fire, Explosion, and

Burn Hazards.

Can cause severe injury, death, or

equipment damage.

Do not set the operating limits of the control outside of

those listed by the appliance manufacturer.