Beckett 7600 AquaSmart Boiler Control User Manual

Page 20

Advertising
background image

20

Figure 16 (continued)- 7600A/B multi-zone connections

with Indirect Domestic Hot Water (DHW)

Control Wiring (Option 1): Circulator-On and -Off Delays on DHW Zone Only

1. Set “DHWP on TT” (see programming section for instructions)
2. Set “C1 on TT” (default, see programming section for instructions)
3. Circulator-on and -off delays will only affect DHW zone.

7600A:

120 VAC BURNER OR

GAS IGNITION SYSTEM

7600B:

24 VAC GAS

IGNITION SYSTEM

L2 L1 C1 C2 ZC ZR B1 B2

TR

TW

SK10022

6

5

4

3

2/N

1/H

T

T

ZONE

RELAY

ZONE

1

LOW VOLTAGE

THERMOSTAT

LOW VOLTAGE

THERMOSTAT

ZONE

2

ZONE

RELAY

T

T

1/H

2/N

3

4

5

6

NEUTRAL

HOT

120 VAC

BLACK

WHITE

P1

CIRCULATOR

120 VAC

P2

CIRCULATOR

120 VAC

CIRCULATOR

120 VAC

P3

P4*

CIRCULATOR

120 VAC

4

3

2/N

1/H

T

T

ZONE

RELAY

ZONE

3*

LOW VOLTAGE

THERMOSTAT

DHW

LIMIT

CONTROL

FIELD/MFR.

SUPPLIED

SERVICE

SWITCH

5

6

◄ CONTINUED FROM PREVIOUS PAGE

CONTINUED ON NEXT PAGE ►

* Additional zones can be added by duplicating

the plumbing and wiring of zone 3.