Installing the 2-in-1 Sensor

For proper operation,

there must be a secure

electrical bond between the green sensor

wire from the sensor and the boiler metal

vessel in direct contact with the boiler

water. Failure to secure an electrical bond

will result in the AquaSmart locking out and

displaying, “LOCKOUT - LOW WATER”.

Explosion,

Burn and Scald Hazards

Excessive water temperatures could cause

explosion, burns, scalding, pressure relief

flooding and fitting leaks.

y

The 2-in-1 Sensor shall only be installed by a

trained professional.

y

The sensor must be installed in the proper

location for correct low water cut-off (LWCO)

operation in accordance with the Boiler

Manufacturer’s instructions.

y

The 2-in-1 sensor body is installed directly into

the boiler wall tapped hole in place of an

immersion well.

y

Carefully follow the outlined procedures for

temperature sensor installation to ensure accurate

water temperature sensing and effective control

operation.

y

Make sure the plumbing for domestic hot water has

anti-scald valve protection.

y

Follow all applicable safety codes, rules and

guidelines for installing an immersion well.

Improper installation can result in the Boiler

overheating.

Do not use in steam

applications. For use in

hot water boilers or water heaters only.

Do not use outside of the intended use

and specifications.

Leak, Burn, and Scald

Hazards

Incompatible thread sealants could severely

damage the sensor threads.

y Only use Teflon

®

Tape or Rectorseal

®

No. 5

®

(soft-set).

y

DO NOT use any anaerobic fast-setting sealants

such as, but not limited to, Loctite

®

, Leak Lock

®

,

Permatex

®

, or Gasoila

®

.

y

Call RWB Technical Services at 1(800)645-2876

to confirm, if unsure.

Note: There are two versions of the 2-in-1 sensor. The

76002N1SXX is an integrated single unit consisting of a

sensor and thermowell. The 76002N1RXX consists of two

components, a thermowell (7600TWXX) and a replaceable

sensor probe (7600PXX). The following instructions apply

to both versions unless otherwise specified.

Part No.

A

Lead Length

B

Insulation Depth

C

Insertion Depth

76002N1[

S/R

]01

8-1/4”

1-1/2”

1-5/8”

76002N1[

S/R

]02

6-1/4”

3-1/2”

1-5/8”

76002N1[

S/R

]05

5”

4-3/4”

1-5/8”

76002N1[

S/R

]06

8-1/4”

1-1/2”

7/8”

Figure 5 - Overall Dimensions & Specifications

Specifications

Storage Temperature Range

-40° to +250°F

Operating Temperature Range

32° to 250°F

Maximum Pressure

250 PSIG

Installation Torque Range (Screw-in)

185 - 200 in/lbs.

◄ 2-in-1 Integrated Sensor (S)

◄ 2-in-1 Field Replaceable (R)

A

C

B