Technical specifications, Temperature ranges and differentials, Environmental ratings – Beckett 7600 AquaSmart Boiler Control User Manual

Page 3: Approvals, Electrical ratings

Advertising
background image

3

AquaSmart Boiler Control Manual

Figure 1 - Getting to know the AquaSmart 7600 Series Control

Temperature Ranges and Differentials

○ High Limit Setting Range: 100 to 220°F (37 to 104°C)

○ High Limit Differential Range: 5 to 45°F (2 to 25°C)

○ Low Limit Setting Range: 100 to 205°F (37 to 96°C)

○ Low Limit Differential Range: 10 to 45°F (5 to 25°C)

○ Factory Range Stops available - consult factory

Environmental Ratings

○ Storage Temperature: -40 to +150°F (-40 to +65°C)

○ Operating Temperature: -4 to +150°F (-20 to +65°C)

7600B at 50 Hz: -4 to +140°F (-20 to +60°C)

○ Maximum Sensing Element Temperature: 250°F (121°C)

○ Relative Humidity: 5 to 85% RH, non-condensing and

non-crystallizing

Approvals

Underwriters Laboratories Listed to UL353,

UL1998 for U.S. and Canada;

CSA C22.2 No. 24

Technical Specifications

Electrical Ratings

Input Voltage: 120 Vac - 50/60 Hz.

Input Current: 0.1 A + B1 + C1 + ZC

MAX Input Current: 20A (Reduce to 15A if optional

power disconnect switch is used)

24 Vac Thermostat Anticipator Current: 0.1 Amp.

Burner Current Rating (B1):

7600A (oil): 7.4 A at 120 Vac FLA; 44.4 A inrush LRA.

7600B (gas): 1.25 A at 24 Vac; 30 VA (total load).

Circulator Current Rating (C1): 7.4 A at 120 Vac FLA;

44.4 A inrush LRA.

Zone Control Current Rating (ZC): 7.4 A at 120 Vac

FLA; 44.4 A inrush LRA.

Do Not Use This Control in

an Application that is Not

Within the Ratings Listed in This Section.

Improper Control Operation May Result.

Electrical Shock Hazard

The AquaSmart control should only be operated with the door attached and securely closed.

Rotate door until grooves

are aligned

Pull door up

T

W

/T

R

Terminals

Communication Port

Sensor Jack

Touch Pad

Power Disconnect Switch (Optional)

Clamping Screw For Sensor

Sensor Mount

Door Removal