Hardware and Software Standby Together

Both types of Standby can be used simultaneously if the AllFrame enters the software version of Standby

first. If while the AllFrame is in software Standby, a hardware contact closure is triggered on the same

AllFrame device, both types of Standby will be in force. On screen in the Device Window, the Standby

Mode

o

N

radio button with be lit and the red

h

ArDwAre

s

tANDBY

A

ctIve

will also be on.

An AllFrame in hardware standby

To exit this state, the hardware contact closure needs to be opened manually (the software Standby will

still be in force). Then, the software Standby can be disabled by either clicking the on‑screen

o

FF

button in

the Device Window or pushing the gray

s

tANDBY

momentary switch on the AllFrame hardware.

Standby and External Clocks

When an AllFrame device is the network’s Control Master and is set to use external AES or Word Clock,

entering standby will force the clock source to be set to Network (internal) clock while the AllFrame is in

standby. When the AllFrame comes out of standby the external clock will again be the network’s clock

source, as long as the C4dio card containing the clock connection is in the same physical location (slot A‑F)

in the AllFrame hardware and the external clock source is still connected.