HI 1746-WS WEIGH SCALE MODULE

2-2

Common-Mode
Rejection

110dB at or below 60 Hz

Common-Mode
Voltage Range

2.5VDC maximum (with respect to earth ground)

Backplane Input
Voltage

5 VDC maximum (with respect to earth ground)

Backplane Current
Load

0.250 Amps at 5 VDC

Power

+5 VDC +/- 5%

C2 Calibration
Input

Isolation from digital section 1000 VDC minimum.

Cable lengths

1000 feet maximum of C2 authorized cable
250 feet maximum of C2 authorized cable (Maximum
of 4 load sensors) with IT Junction box.

Load Cell
Excitation

5 VDC +/- 1.15 W maximum.
Isolation from digital section 1000 VDC minimum

C2 Calibration
Output

Isolation from digital section 1000 VDC minimum

Set Point (1 & 2)
Out

Discrete outputs (TTL) step function of 0 or +5 VDC
to drive an SSR

Environmental
Requirements

Temperature
Coefficient

Less than 0.005% of full scale per degree C for Cal-
LO and Cal-HI reference points

Operating
Temperature
Range

0

o

C to 60

o

C (32

o

F to 140

o

F)

Storage
Temperature
Range

-20

o

C to 85

o

C (-4

o

F to 185

o

F)

Humidity Range

0-90% (non-condensing)