Chapter 5 - Calibration

5-7

N10:40 - 46

Location of data being written to M0 File.

N10:60 - 72

Locations of Parameters Values

N10:60

Units

N10:61

Number of Averages

N10:62

WAVERSAVER Setting

N10:63-64

0 Tolerance

N10:65-66

A0 Tolerance

N10:67-68

Motion

N10:69-70

CalLo

N10:71-72

Span

C2 Calibration
Ladder Logic
Explanation

This file will download and set a reference point for
C2 calibration and then save data to non-volatile
memory.

Rung #0

Does an initial read of the M1 file.
this is necessary to get the sequence
number for future writes.

Rungs #1-5

Downloads a reference point value.
These rungs follow the same pattern
as the SETPARAMS example in
Chapter 4.

Rungs #6-12

Writes the C2CALCMD to set the ref-
erence point. These rungs follow the
same pattern as setting a parameter in
the SETPARAMS example in Chapter
4.

Rungs #13-17 Writes the WRITENONVOLATILE

command. This will save the new cal-
ibration to the non-volatile memory.
These rungs follow the same pattern
as setting a parameter in the SET-
PARMS example in Chapter 4.