Fluke 900 User Manual

Page 39

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

FLUKE 900 SERVICE MANUAL

Selftest

/SHORT is checked to see if the line is hi^ (ie. not shorted to ground). /SYNCEN and
/RELEN are tested by having sync latches or relays cause a fault and verifying that the fault
occurred.

Four bytes of test results are presented:

BYTE 0

b7 thru 5-0 (not used)
b4 -/STRFRQ output ofTC PAL not woiking
b3 - Interrupts failed
b2 - /SYNCEN line test failed
bl - /SHORT test failed
bO - /RELEN test failed
NOTE: only interrupts generated by TIME port are tested.

BYTE 1

b7 thru 3 - 0 ( not used )
b2 - test time timer
bl -10 ms timer
bO -1 ms timer

Each bit in bytes 2 and 3 corresponds to one execution of the test cycle, set up to produce the
expected results. If any bit in bytes 2 or 3 is set it means that results were not as expected. For
example, if b6 in byte 2 is set it means that the gate function was observed to be not active or
faults were detected. Trigger is programmed with one word Gevel) in byte 2 trigger test; for
byte 3, trigger is programmed with two words (edge). For aU W2 related tests (byte 3 bits 3
thru 0), W1 always occurs.

BYTE 2

b7 - gate did not occur no faults
b6 - gate occurred no faults
b5 - gate did not occur, fatilts
b4 - gate occurred, faults
b3 - trigger did not occur, no faults
b2 - trigger occurred, no fault
bl - trigger did not occur, faults
bO - trigger occurred, faults

BYTE 3

b7 - trigger W1 did not occur, no faults
b6 - trigger W1 occurred, no faults
b5 - trigger W1 did not occur, faults
b4 - trigger W1 occurred, faults
b3 - trigger W2 did not occur, no faults
b2 - trigger W2 occurred, no faults
bl - trigger W2 did not occur, faults

bO - trigger W2 occurred, faults

3 - 1 5

Advertising