6|f|8ia0i8,6i9i, Toshiba – Toshiba LF600F User Manual

Page 100

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

TOSHIBA

6|F|8iA0i8,6i9i

Changing the high, low, high-high, or low-low limit alarm value

Shown below is an example of changing the high limit alarm value from +105% to +103%.

Key operation

Display example

Description

I:

MEAS MODE
HALM SET

ALM VAL

LALM SET
L ALM VAL

[SEL] [ENT]

Select "HALM VAL" in the configuration item

selection screen.

STEP1

[ENT]

I2:

HALM VAL

+105.0

%

[EXT] [ENT]

The currently set value (+105.0 in this example) is

displayed.

Then press the [ENT] key.

* Pressing the [EXT] key returns you to the menu
screen.

STEP2

[ENT]

I2:

HALM VAL

B105.0

%

[U P] [SEL] [SET]

The switch name display at the bottom changes

(three keys [UP], [SEL] and [SET]).

At the same time, the cursor appears.

(The digit on which the cursor is positioned is

reverse-displayed.)

STEPS

[SEL]0[UP]

12:

H ALM VAL

+10|.0

%

[U P] [SEL] [SET]

Move the cursor to the desired digit using the [SEL]

key and change the numeric value using the [UP]

switch.

Repeat this operation to change the value to

+103.0%.

When you have selected the desired item, press

the [SET] key to set the value temporarily.

STEP4

[SET]

12:

H ALM VAL

+103.0

%

OK?

^

[NOl [SETl

When you press the [SET] key, a message
confirming you whether the setting is OK is

displayed.

If OK, press the [SET] key. If you want to redo the

setting, press the [NO] key.

STEP5-1

[NO]

12:

H ALM VAL

B105.0

%

[U P] [SEL] [SETl

Pressing the [NO] key when you are asked "OK?"

causes the numeric value to return to the previous

value and enables you to redo the setting.

STEP5-2(=END)

[SET]

12:

HALM VAL

+103.0

%

[EXT] [ENT]

Pressing the [SET] key when you are asked "OK?"

causes the setting to be determined.

Press the [EXT] key. You return to the menu

screen.

Pressing the [ENT] key enables you to restart
setting value change operation from a state of

+103.0%.

Note: If you set a value that is not within a range of -10% to +110%, * LOW OVER SPEC* or

♦HIGH OVER SPEC* is displayed and the value returns to the one before change. Set a

value once again.

-

99

-

Advertising
This manual is related to the following products: