2 exciting current vaiue, 2 exciting current value, Toshiba – Toshiba LF600F User Manual

Page 56

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

TOSHIBA

6iFi8iA0i8|6|9,

8.2.2 Exciting Current Vaiue

The exciting current value can be checked/changed by the following procedures.

Be sure to match the exciting current value with the value specified for the
combined detector.
Specifying any other value may cause an error.

Shown below is an example of changing the exciting current value from 0.1900A to 0.2150A.

Key operation

Display example

Description

A:

In the configuration items selection screen, select

MEAS MODE

^EX CURRENT

METER SIZE
EX FREQ
FLOW DIRECTN
PASSWORD

ADDR SET

[SEL] [ENT]

"EX CURRENT."

STEP1

A1;

The currently set exciting current value (in this

EX CURRENT

0.20000

example 0.1900A) is displayed.

[ENT]

A

Then press the [ENT] key.

* Pressing the [EXT] key returns you to the menu

[EXT] [ENT]

screen.

STEP2

A1:

The switch name display at the bottom changes.

EX CURRENT

.|1900

(three keys [UP], [SEL] and [SET])

At the same time, the cursor appears.

[ENT]

A

(The digit in the place the cursor position is

currently positioned is reverse-displayed.)

fU P] [SEL] [SET!

Then press the [SEL] key.

STEPS

A1:

You can continue to change the setting value.

EX CURRENT

Press the [SEL] key to move the cursor to the digit

O.09OO

you want to change.

[SEL]

A

fU PI [SEL] fSETl

Then press the [UP] key.

STEP4

A1:

EX CURRENT

You can continue to change the setting value.

0.@900

Pressing the [UP] key increments the digit in the

[UP]

A

fU P] [SELl [SET!

place the cursor is currently positioned. (Holding

down this key causes this increment operation to be
continued).

-

55

-

Advertising