8.2.16 Current Output Setting Used When an Alarm Occurs

In case an alarm occurs with the self-diagnostic function, the current output value will be flxed
to the selected value.

Select the current output value used in case an alarm occurs from the following table.

# Current output setting function in case an alarm occurs

Selection

Current output settinq used when an alarm occurs

UNDER 3.0mA

3.0mA or less

4.0mA

4.0mA

TTOD

Fixed to the selected value

OVER 24.0mA

24.0mA or more

The current output value at alarm generation can be checked/changed by the following procedure.

Shown below is an example of changing the setting from UNDER 3.0mA to 4.0mA.

Key operation

Display example

Description

D:

Select "ALM mA SET" in the configuration item selection

MEAS MODE

screen.

DAMPING
LOW CUT

^ALM mA SET

DSP LOW CUT
LOW LIMIT

____ [SEU_____ [EMI]____

STEP1

I D3:

The current setting value (UNDER 3.0mA in this example)

ALMmASET

is displayed.

UNDER 3.0mA

[ENT]

Then press the [ENT] key.

[EXT]

[ENT]

* Pressing the [EXT] key returns you to the menu screen.

STEP2

D3:

The switch name display at the bottom changes (three

I

ALMmASET

keys [UP], [DWNL] and [SET])

UNDER 3.0mA

At the same time, the cursor appears.

[ENT]

(The digit on which the cursor is positioned is

reverse-displayed.)

I

fU PI fDWN] [SET]

I

STEPS

D3:

Change the selection item using the [UP]/[DWN] key.

ALM mA SET

BiM

When you have selected the desired item, press the [SET]

[UP]/[DWN]

key.

[U P] fDWNl [SET]

STEP4

D3:

When you press the [SET] key, the selected item is set

ALM mA SET

temporarily and a message confirming you whether the

4,0mA

setting is OK is displayed.

[SET]

If OK, press the [SET] key. If you want to redo the setting.

OK?

W

press the [NO] key.

____[NOl [SET]__________

STEP5-1

D3:

Pressing the [NO] key when you are asked "OK?" causes

ALM mA SET |

the setting value to return to the previous value and

UNDER 3.0mA

enables you to redo the setting.

[NO]

i

[U P] [DWNl [SET]

I

STEP5-2(=END)

D3:

Pressing the [SET] key when you are asked "OK?" causes

ALM mA SET

the setting to be determined.

4.0mA

Then, press the [EXT] key. You return to the menu screen.

[SET]

Pressing the [ENT] key enables you to restart

[EXTl [ENTI

setting operation from a state of 4.0mA.