Cisco XR 12406 User Manual

Page 225

Advertising
background image

A-3

Cisco XR 12406 Router Installation Guide

OL-13831-01

Appendix A Cisco XR 12406 Router Technical Specifications and Warnings

Specifications

Caution

To ensure that the chassis configuration complies with the required power
budgets, use the on-line power calculator. Failure to properly verify the
configuration may result in an unpredictable state if one of the power units fails.
Contact your local sales representative for assistance.

The electrical specifications and values listed in

Table A-3

are for a Cisco XR

12406 Router system equipped with the DC-input PDU and DC-input power entry
modules (PEMs).

Caution

To ensure that the chassis configuration complies with the required power
budgets, use the on-line power calculator. Failure to properly verify the
configuration may result in an unpredictable state if one of the power units fails.
Contact your local sales representative for assistance.

1.

For each AC-input power supply module.

Table A-3

DC Power Entry Module Electrical Specifications

Description

Value

Rated input voltage

1

1.

For each DC-input PEM.

–48 VDC nominal in North America

–60 VDC nominal in the European Community

(range: –40.5 to –75 VDC)

Input current rating

1

60A maximum @ 40.5 VDC

Source DC service
requirement

1

60A

Nominal output voltage
and current

–48 VDC @ 40A maximum

Total DC input power

1630 VA (original series)

2600 VA (enhanced series)

Redundancy

2 DC-input PEMs are required for 2N redundancy