Ventilation – Cisco XR 12406 User Manual

Page 76

Advertising
background image

Chapter 2 Preparing for Installation

Installation Site Requirements

2-12

Cisco XR 12406 Router Installation Guide

OL-13831-01

Ventilation

The blower module is mounted at the rear of the chassis; air flow to the air filters
and blower module should not be blocked.

Note

Warm air is exhausted from the rear of the chassis. Maintain 6 inches (15.24 cm)
of clearance at both the inlet and exhaust openings on the chassis to allow
sufficient air flow.

When placing multiple a Cisco XR 12406 Router in the same rack, ensure that
there is sufficient ventilation to accommodate the routers.

Equipment located near the bottom of the rack can generate excessive heat
that is drawn upward and into the intake ports of equipment above, possibly
leading to overheating.

The heated exhaust air from other equipment can enter the inlet air vents and
cause overheating inside the router.

A ventilation system that is too powerful in an enclosed rack can also prevent
cooling by creating negative air pressure around the chassis and redirecting
the air away from the air intake vent. If necessary, operate the router with the
rack door open or in an open rack.

The correct use of baffles inside an enclosed rack can assist in cooling the
router.

Advertising