DMX512 REFERENCE GUIDE

21

Current Requirements

Current calculations are required to ensure that the system has adequate circuit breaker safety control. The AC line
disconnect has a 200A circuit breaker to handle the Series 300 Modular Racks and Series 200 ACS racks. Depending
on the quantity and type of luminaires and the voltage used, the current varies. Although the maximum operating limit
for the AC line disconnect is 200A, we recommend that continuous operating current does not exceed 150A. This will
avoid tripping the circuit breaker. Systems drawing power in excess of 150A will require multiple modular racks, ACS
racks and AC line disconnects. The same is true for the 30A mini-ACS line disconnect. We recommend that
continuous operating current does not exceed 20A.

Equipment current requirements vary with the AC line voltage available. Linear voltage regulators dissipate more
power at higher line voltages and consume more current. Switch-mode regulators maintain constant power into a
load and consume more power at lower line voltages. Some power is lost in long cable runs, resulting in lower line
voltages at the equipment, with the corresponding impact on current requirements. Two factors determine the current
requirements of a system: output voltage of the modular rack and ACS rack and number and type of luminaires in the
system.

Current Calculation

The current requirements for VARI

❋LITE equipment are provided here. For Series 300 luminaires, the current

requirement is expressed as the current draw on a Smart Repeater unit that is fully loaded with six luminaires with
each luminaire operating all motors (a maximum power draw scenario). All VARI

❋LITE Series 200/300 AC voltage

selector boards are designed to operate the equipment within one of three voltage ranges: 80 to 130 VAC, 170 to 260
VAC, or 80-260 VAC.

Because of the complexities of calculating three-phase power requirements, this data will never be 100% accurate,
and is intended for guidance only. It is recommended that a 20% headroom allowance be added to the final phase
figures to allow for imbalances.

CAUTION:

Only 50 VL2B and VL2C luminaires may be connected to a Series 200 ACS rack and only nine

may be connected to a mini-ACS rack due to the current requirements.

CAUTION:

To avoid damage to equipment and to ensure proper equipment operation, consult with local

staff regarding power concerns.

Equipment

120 Volts Phase to

Neutral60 Hz Wye Mode

208 Volts Phase to

Phase60 Hz Delta Mode

240 Volts

Phase to Neutral

l50 Hz Wye Mode

VL2C Luminaire

11.0 amps

6.5 amps

6.3 amps

VL4 Luminaire

8.0 amps

4.8 amps

4.5 amps

Smart Repeater

9.6 amps

5.2 amps

6.0 amps

Smart Repeater Plus

12.8 amps

7.2 amps

6.5 amps

DMX200

1.0 amps

0.2 amps

0.3 amps

SPC-36 Controller

1.0 amps

0.2 amps

0.3 amps

APS6 Module (400W)

6.7 amps

3.7 amps

3.6 amps

APS6 Module (625W)

9.5 amps

5.5 amps

5.1 amps

APS6 Module (700W)

11.5 amps

5.8 amps

7.4 amps

C3 Module (1000W)

N/A

4.7 amps

4.3 amps

C3 Module (1200W)

N/A

5.2 amps

5.1 amps

DMX Power Pack

10.0 amps

6.0 amps

5.0 amps