Ring Redundancy

20

2.2 Example of MRP-Ring

PSSnet SHL - Redundancy Configuration

Pilz GmbH & Co. KG, Felix- Wankel Str. 2, 73760 Ostfildern

Note: Configure all the devices of the MRP-Ring individually. Before you
connect the redundant line, you must complete the configuration of all the de-
vices of the MRP-Ring. You thus avoid loops during the configuration phase.

…

Set up the network to meet your requirements.

…

You configure all 6 ports so that the transmission speed and the duplex
settings of the lines correspond to the following table:

Bit rate

100 Mbit/s

1000 Mbit/s

Autonegotiation
(automatic configuration)

off

on

Port

on

on

Duplex

Full

Table 3: Port settings for ring ports

…

Select the Redundancy:Ring Redundancy dialog.

…

Under “Version”, select MRP.

…

Define the desired ring ports 1 and 2 by making the corresponding
entries in the module and port fields. If it is not possible to enter a
module, then there is only one module in the device that is taken
over as a default.