Pilz PSSnet SHL 8T MRP User Manual

Page 49

Advertising
background image

Ring/Network coupling

PSSnet SHL - Redundancy Configuration

Pilz GmbH & Co. KG, Felix- Wankel Str. 2, 73760 Ostfildern

3.2 Preparing a Ring/Network cou-

pling

49

The displays in the “Information” frame mean

(see fig.

23)

:

– “Redundancy existing”: One of the lines affected can fail, as a

redundant line will then take over the function of the failed line.

– “Configuration failure”: The function is incomplete or incorrectly

configured.

To avoid continuous loops, the Switch sets the port state of the coupling
port to “off” if you:
– switch off operation or
– change the configuration
while the connections are in operation at these ports.
Note: The following settings are required for the coupling ports (you
select the Basic Settings:Port Configuration dialog):

– Port: on
– Automatic configuration (autonegotiation):

on for twisted-pair connections

– Manual configuration: 100 Mbit/s FDX

for glass fiber connections

Note: If VLANS are configured, note the VLAN configuration of the
coupling and partner coupling ports.
In the Network/Ring Coupling configuration, select for the coupling and
partner coupling ports
– VLAN ID 1 and “Ingress Filtering” disabled in the port table and
– VLAN membership U in the static VLAN table.

Redundancy mode
…

In the “Redundancy Mode” frame, select

(see fig.

25)

– “Redundant Ring/Network Coupling” or
– “Extended Redundancy”.

Advertising
This manual is related to the following products: