Ring/Network coupling

34

3.2 Preparing a Ring/Network cou-

pling

PSSnet SHL - Redundancy Configuration

Pilz GmbH & Co. KG, Felix- Wankel Str. 2, 73760 Ostfildern

Note: The following settings are required for the coupling ports (you
select the Basic Settings:Port Configuration dialog):

– Port: on
– Automatic configuration (autonegotiation):

on for twisted-pair connections

– Manual configuration: 100 Mbit/s FDX

for glass fiber connections

Note: If VLANS are configured, note the VLAN configuration of the
coupling and partner coupling ports.
In the Network/Ring Coupling configuration, select for the coupling and
partner coupling ports
– VLAN ID 1 and “Ingress Filtering” disabled in the port table and
– VLAN membership U in the static VLAN table.

Redundancy mode
…

In the “Redundancy Mode” frame, select

(see fig.

11)

– “Redundant Ring/Network Coupling” or
– “Extended Redundancy”.

Figure 11: Selecting the redundancy mode

With the “Redundant Ring/Network Coupling” setting, either the main
line or the redundant line is active. Both lines are never active simulta-
neously.