Ring/Network coupling

PSSnet SHL - Redundancy Configuration

Pilz GmbH & Co. KG, Felix- Wankel Str. 2, 73760 Ostfildern

3.2 Preparing a Ring/Network cou-

pling

45

The coupling between two networks is effected by the main line (thick blue
line). If the main line fails, the redundant line (thick blue dotted line) takes
over coupling the two networks.
The coupling is effected by two Switches.
The Switches send their control packets via a control line.
The device to which you connect the main line, and the device to which you
connect the redundant line, are partners as regards the coupling.

…

Connect the two partners via their ring ports.

…

If the STANDBY DIP switch is OFF, connect the main line to the coupling
port.

…

Select the Redundancy:Ring/Network Coupling dialog.

…

Select two-Switch main coupling
with control line

(see fig.

22)

.

Figure 22: Two-Switch coupling with control line

1: Coupling port
2: Partner coupling port
3: Control line

The following settings apply to the Switch displayed in blue in the
selected graphic.
…

Select the coupling port

(see fig.

23)

,

(see table

9)

.

With “Coupling port” you specify at which port you are connecting
the redundant line.

…

Select the control port

(see fig.

23)

,

(see table

9)

.

With “Control port” you specify at which port you are connecting the
control line.