Ring/Network coupling

PSSnet SHL - Redundancy Configuration

Pilz GmbH & Co. KG, Felix- Wankel Str. 2, 73760 Ostfildern

3.2 Preparing a Ring/Network cou-

pling

39

Note: Configure the coupling port and the redundancy ring ports on different
ports.

…

Activate the function in the “Operation” frame

(see fig.

16)

.

…

You now connect the redundant line.

The displays in the “Select port” frame mean

(see fig.

16)

:

– “Port mode”: The port is either active or in stand-by mode.
– “Port state”: The port is either connected or not connected.
– “IP Address”: The IP address of the partner, if the partner is already

operating in the network.

The displays in the “Information” frame mean

(see fig.

23)

:

– “Redundancy existing”: One of the lines affected can fail, as a

redundant line will then take over the function of the failed line.

– “Configuration failure”: The function is incomplete or incorrectly

configured.

Figure 16: Selecting the port and enabling/disabling operation

To avoid continuous loops, the Switch sets the port state of the coupling
port to “off” if you:
– switch off operation or
– change the configuration
while the connections are in operation at these ports.