Type 2 message examples – Applied Motion RS-232 User Manual

Page 293

Advertising
background image

293

920-0002 Rev. I

2/2013

Host Command Reference

Type 2 Message Examples

Example

1:

parameter

write

AC100

set acceleration rate to 100 rev/sec/sec (6000 rpm/sec)

opcode

0x83 parameter write, from Table 2

operand

0x1E

from

Table

3

data

0x258 units are 10 rpm/sec, so 6000/sec is represented by 600 decimal = 258 hex

Type 2 Command Message Payload

Type 2 Response Message Payload

byte 0

0

reserved

byte 0

0

reserved

byte 1

2

message type

byte 1

2

message type

byte 2

83

opcode

byte 2

83

opcode

byte 3

1E

operand

byte 3

1E

operand

byte 4

2

data MSB

byte 4

?

Status Code MSB

byte 5

58

data LSB

byte 5

?

Status Code LSB

byte 6

0

not used

byte 6

0

not used

byte 7

0

not used

byte 7

0

not used

Example

2:

parameter

read

AC

read back the acceleration rate

opcode

0x84 parameter read, from Table 2

operand

0x1E

from

Table

3

return value

0x258 units are 10 rpm/sec, so 6000/sec is represented by 600 decimal = 258 hex

Type 2 Command Message Payload

Type 2 Response Message Payload

byte 0

0

reserved

byte 0

0

reserved

byte 1

2

message type

byte 1

2

message type

byte 2

84

opcode

byte 2

84

opcode

byte 3

1E

operand

byte 3

1E

operand

byte 4

0

not used

byte 4

2

read data MSB

byte 5

0

not used

byte 5

58

read data LSB

byte 6

0

not used

byte 6

0

not used

byte 7

0

not used

byte 7

0

not used