BINDER M 53 User Manual

Page 32

Advertising
background image

M (E2) 10/2014

page 32/71

9.2 Selecting between set-point ramp and set-point step

Temperature set-points always refer to the start of a program section, i.e., at the beginning of each pro-

gram section the entered temperature set-point is targeted. During program section operation, the tem-

perature gradually passes to the set-point entered for the next program section.
By appropriate planning of the program section timing, you can enter all kinds of temperature transitions.

Gradual temperature changes “set-point ramp”
The set-point changes its value gradually while proceeding from one program section to the next one

during the programmed section length. The actual temperature value (X) follows the continually mov-

ing set-point (W) at any time.

Program sections with constant temperature
The initial values of two subsequent program sections are identical; so the temperature remains con-

stant during the whole time of the first program section.

Sudden temperature changes “set-point step”
Steps are temperature changes (ramps) that occur during a very short interval. A section with a differ-

ent set-point follows two program sections with an identical set-point. If the duration of this transitional

program section is very short (minimum entry 1 sec), the temperature change will proceed rapidly

within the minimum amount of time.

01

02

03

04

05

06

07

08

09

W

t

Figure 7: Possible temperature transitions


The following chapter offers examples of programming a set-point ramp and a set-point step.

9.3 Program entry as set-point ramp or as set-point step

In order to avoid incorrect programming, we recommend plotting the temperature profile (chart template

in chap. 9.9) and entering the values into a table (templates in chap. 9.10).
The controller provides 8 operation lines that can be activated or de-activated for each program section.

Operating contact 1 is used to control the air flap position (ON = Air flap open, OFF = Air flap closed). The

other operation lines are non-functional.
The unit does not provide active refrigeration, but you can program defined cooling down ramps within

the range of possible cooling-down times , e.g. in order to avoid tension in the material.

Advertising
This manual is related to the following products: