9 technical features, Technical features – CIRCUTOR MDC-20 User Manual

Page 55

Advertising
background image

MDC-20

User Manual

Page 55 of 58

9

TECHNICAL FEATURES

Power supply of the unit

Single-phase

85…264V~ / 120…300V

Frequency

50/60 Hz

Consumption

5…8VA (depending on the number of connected
relays)

Installation category

Category III according to EN 61010.

Double-insulated electric shock protection class II.

Inputs

Type

Potencial free contact - NPN

Insulation

Optoisolated

Duration of metering impulses

Minimum 50 ms

Time between impulses

Minimum 50 ms

Maximum frequency of impulses

10 Hz

Outputs

Type

Relay

Maximum power of operation

750 VA

Maximum voltage of operation

250 Vac

Maximum current AC1 (resistive load)

5 A

Electrical life (250 Vac / 5A)

3 x 10

4

operations

Mechanical working life

2 x 10

7

operations

Screen

Type

LCD, Alphanumeric, 2 lines of 20 characters, with backlight

Communications

Channels

1 Ethernet channel + 1 RS485 channel

Ethernet channel

Type

Ethernet 10BaseT / 100 Base TX self-detecting

Connector

RJ-45

Network protocols

HTTP/ Modbus RTU