12.1.4. Mains inrush current limiter

The Main Power Supply is started softly to limit inrush current. Up

to two D80 may be powered up at the same time without

triggering a line circuit breaker of 13-16 A (230 V) or 30 A

(100-120 V) respectively. Inrush current is limited to:

13 A 

RMS

@ 230 V AC

22 A 

RMS

@ 120 V AC

27 A 

RMS

@ 100 V AC

12.1.5. Mains supply requirements

Due to the high power capability of the amplifier, properly

dimensioned mains supply installation and distribution are

essential.

However, the mains supply benefits from the built-in active PFC

(Power Factor Correction) function of the amplifier, which causes

an almost ideal (sinusoidal) current shape. Power losses of the

mains supply and cables are kept to the lowest possible minimum.

Due to its automatic mains voltage selection, the amplifier can be

fed from all usual mains voltages within the rated ranges as stated

in Þ Chapter 12.1.2. "Automatic mains range selection"

on page 68. Within these ranges, the mains voltage does not

affect average output power figures due to the built-in regulated

power supply. However, the dynamic character of common audio

signals may cause short-time power peaks being twice as high as

the average values. The resulting higher current draw causes an

increased voltage drop on the mains line which may reduce the

available output power if it gets too high.

To ensure safe and stable operation, observe the following

recommendations and specifications:

Operate a single amplifier on a 16 A circuit breaker at 208 to

240 V (high range) or on a 30 A circuit breaker at 100 to

127 V (low range).

Operate the amplifier at a high-range supply (208 to 240 V),

if possible. A low-range supply (100 to 127 V) requires a

cable cross section that is 4 times higher to achieve

comparable power performance.

When three amplifiers are operated with a three-phase

(120°) mains supply, the current on the N (neutral) conductor

can be minimized by matching loads and signals between the

three devices.

Keep the supply line as short as possible and its cross section

as high as possible, especially when operating the device at

100 to 127 V. Voltage drop at full load (30/15 A at

115/230 V) should not exceed 5 %. For reference

specifications, refer to the following table.

d&b D80 Manual 1.9 en

69