HORIZONTAL CORNER INSTALLATION

FIGURE 4

PELLET VENT

OPTIONAL AIR INTAKE

CHIMNEY CAP

The exhaust vent termination on either vertical or horizontal installations shall be located as follows:

A minimum of 4 feet (1219 mm) below or beside and a minimum of 1 foot (305 mm) above any door
or window that opens, or any opening into a building.

A minimum of 2 feet (610 mm) from any adjacent building.

A minimum of 7 feet (2134 mm) above grade, when located adjacent to public walkways.

A minimum of 2 feet (610 mm) above grass, plants or other combustible surfaces.