NOTE:

Masonry fireplace installations require a direct connection or positive (complete reline) connection to the
chimney flue. With a direct connection a block-off plate made of metal or other non-combustible material
(i.e. Kaowool or high temperature fiberglass insulation) must be used at the damper location and sealed
airtight. The singlewall pipe or flexible liner must extend past the block-off plate or insulation by one (1) foot
(305 mm) or to the first flue tile if the chimney has a tile lining.

With a positive connection, the block-off plate at the damper location is optional, but a sealed cover plate
is required at the top of the chimney. A positive connection (complete reline) is recommended for ease of
cleaning. Zero clearance (metal) fireplace installations require a complete reline to top of chimney.

HEARTH STOVE INSTALLATION INTO EXISTING

MASONRY & ZERO CLEARANCE (METAL) FIREPLACE

SEAL COVER PLATE TO
CHIMNEY WITH SILICONE
SEALER.

3" STAINLESS STEEL SINGLE
WALL PIPE OR FLEXIBLE
LINER CAN BE USED.
(SEE NOTE BELOW).

SINGLE WALL TEE CAN BE
USED AS AN OPTION.

6" MIN.

(152mm)

FIGURE 7

POSITIVE CONNECTION
(COMPLETE RELINE)

BLOCK-OFF PLATE OR
NON-COMBUSTIBLE
MATERIAL MAY BE USED
AT THE FIREPLACE
DAMPER LOCATION. THIS
SEAL MUST BE AIRTIGHT.
(SEE BELOW)

12"

TERMINATION OF
DIRECT CONNECTION.

OPTIONAL