INSERT INSTALLATION - ZERO CLEARANCE (BUILT-IN)

(CONTINUED)

The pellet vent must maintain a 3" clearance from any combustible. Make sure to follow the clearance specified by the
manufacturer for the factory built chimney when making the opening in the roof. Whenever a ceiling or floor is penetrated
an approved thimble or firestop with 3" clearance must be used. See the illustration below for other specifications that must
be met.

Flashing

3" Min.

OPTION 1.
Wall or Ceiling
Thimble

OPTION 2.
Firestop With 3"
(76mm) Clearance

24" Min.

Floor Shield

Optional Flue Direction
(Requires an increase
in the minimum framing
dimension) - Must Have
Non-Combustible
Material Under the Tee.

3"
Min.

3"
Min.

Keep Clearance Specified
By Factory Built Chimney
Manufacturer

Pellet Vent

HEARTH
RQUIREMENT
0" FROM
FRONT OF
INSERT