READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR
NEW HEATER. FAILURE TO FOLLOW THE INSTRUCTIONS MAY RESULT
IN PROPERTY DAMAGE, BODILY INJURY, OR EVEN DEATH.

Check with local building officials for any permits required for installation of this pellet heater
and notify your insurance company before proceeding with installation.

P

LANNING

T

HE

I

NSTALLATION

HINT:

We suggest that you have an authorized Travis Industries dealer
install your heater. If you install the heater yourself, your authorized
dealer should review your plans for installation.

The Avalon 900 PI insert was designed to be installed into an existing masonry or zero-clearance
(metal) fireplace, or built directly into the wall (see the section "Built-In Installation"). The
requirements listed below are required for every type of installation and must be followed. In
addition, each type of installation has unique requirements that must be met besides the
requirements listed below. Hence, it is very important to follow the requirements listed in the
section "Insert Requirements" and the installation instructions specific to the type of
installation
being used. Make a sketch of your installation including dimensions before
installing to double-check against the requirements listed.

I

NSERT

P

LACEMENT

R

EQUIREMENTS (See the illustration below)

¥

The insert must be placed so that no combustibles are within, or can swing within
(e.g. drapes, doors), 36" of the front of the heater

¥

Insert and floor protection must be installed on a level, secure floor

¥

The insert must maintain a 9" clearance to sidewalls

¥

The non-combustible side facing must extend 8" from the side of the insert

¥

The non-combustible top facing must extend 12" above the top of the insert

¥

The combustible mantle must be at least 13" above the top of the insert

12" Min.

13" Min.

8" Min.

Combustible Mantle

Floor protection must
extend underneath
insert to the faceplate

9" Min.

Sidewall

21 1/4" Min.
(Width of Floor Protection)

WIDTH INCLUDING SIDE PANELS:
40 3/8" with 8"x10" Panels
44 3/8" with 10"x13" Panels

HEIGHT INCLUDING
TOP PANEL:
28 7/8" with 8"x10" Panels
31 7/8" with 10"x13" Panels