HINT:

REDUCING CLEARANCES - Clearances may be reduced by
methods specified in NFPA 211, listed wall shields, pipe shields, or
other means approved by local building or fire officials.

The stove must be placed so all of the requirements below are met:

¥

Heater must be placed so that no combustibles are within, or can swing within,
36" of the front of the heater (e.g. drapes, doors)

¥

Heater and floor protection must be installed on a level, secure floor

STRAIGHT INSTALLATION (see the illustration below)

A

9" clearance from the heater to the sidewall

B*

3" clearance from the heater to the backwall and the pellet vent must maintain the
clearance outlined in clearance C below

C*

The pellet vent must maintain a 3" clearance to any wall except when passing
through an approved thimble.

CORNER INSTALLATION (see the illustration below)

C*

The pellet vent must maintain a 3" clearance to any wall except when passing
through an approved thimble.

G*

2" from the rear corner of heater to the cornerwall

*

If an interior vertical pellet vent is being used, the clearance to the backwall is determined by
the upward-turning elbow or "Tee". It will vary in depth depending on the brand of pellet
vent used. Before establishing the heater placement, connect the elbow or "Tee" and measure
off the 3" clearance to the backwall to establish the heater position.

The center flue adapter allows the stove to be located closer to the backwall
(measurement "B") when using an interior vertical pellet vent. For corner
installations, the adapter must maintain a 3" clearance to the cornerwall . For
straight installations the following dimensions can be used to determine the
heater location:
DIAMETER OF VENT:

3"

6"

BACKWALL TO STOVE MAY BE A MIN. OF:

7"

9"

Floor protection

Cornerwall

Cornerwall

G

D

Door
Opening

C

E

F

G

Backwall

Sidewall

A

B

C

D

Door
Opening

Floor protection

E

F

Interior
Vertical
Pellet Vent

Direct or
Exterior
Vertical
Pellet Vent

CORNER

I N S T A L L A T I O N

STRAIGHT

I N S T A L L A T I O N