Return query data, Restart communications option, Listen only mode – Basler Electric BE1-851 Modbus Protocol User Manual

Page 12

Advertising
background image

1-4 BE1-851

Modbus

Protocol

9289900992 Rev F

Data Lo
Data Hi
Data Lo
CRC Hi error check
CRC Lo error check

Return Query Data

This query contains data to be returned (looped back) in the response. The response and query
messages should be identical. If the query is a broadcast (device address = 0), no response message is
returned.

Device Address
Function Code =

08 (hex)

Subfunction Hi =

00 (hex)

Subfunction Lo =

00 (hex)

Data Hi =

xx (don't care)

Data Lo =

xx (don't care)

CRC Hi error check
CRC Lo error check

Restart Communications Option

This query causes the remote communications function of the BE1-851 to restart, terminating an active
listen only mode of operation. No effect is made upon primary relay operations. Only the remote
communications function is affected. If the query is a broadcast (device address = 0), no response
message is returned.

If the BE1-851 receives this query while in the listen only mode, no response message is generated.
Otherwise, a response message identical to the query message is transmitted prior to the
communications restart.

Device Address
Function Code =

08 (hex)

Subfunction Hi =

00 (hex)

Subfunction Lo =

01 (hex)

Data Hi =

xx (don't care)

Data Lo =

xx (don't care)

CRC Hi error check
CRC Lo error check

Listen Only Mode

This query forces the addressed BE1-851 to the listen only mode for Modbus

™ communications, isolating

it from other devices on the network. No responses are returned.

While in the Listen Only mode, the BE1-851 continues to monitor all queries. The BE1-851 does not
respond to any other query until the listen only mode is removed. All write requests with a query to Preset
Multiple Registers (Function Code = 16) are also ignored. When the BE1-851 receives the restart
communications query, the Listen Only mode is removed.

Device Address
Function Code =

08 (hex)

Subfunction Hi =

00 (hex)

Subfunction Lo =

04 (hex)

Data Hi =

xx (don't care)

Data Lo =

xx (don't care)

CRC Hi error check
CRC Lo error check