System data setting parameters, Breaker duty setting parameters, Relay data setting parameters – Basler Electric BE1-851 Modbus Protocol User Manual

Page 50

Advertising
background image

3-12 BE1-851

Modbus

Protocol

9289900992 Rev F

† When Password Security in enabled, relay parameters can be changed via Modbus

™ only if access is

obtained via the Access Password and Access Request holding registers, and released via the Exit
register with value 89 (ASCII character “Y”).

System Data Setting Parameters

41019

System

Frequency

SI

Read

and

Write:

50 for 50 hertz

60 for 60 hertz


41020

Phase

Rotation

SI

Read

and

Write:

1 for ABC rotation

2 for ACB rotation


41021

Phase

CT

Ratio

INT

41022

Neutral

CT

Ratio INT

Read

and

Write:

1 to 50,000

Breaker Duty Setting Parameters

41092

Breaker

Duty

Type

FP

Read

and

Write:

0

for

Off

1 for Sum I, primary centi-amps

2 for Sum I

2

, primary centi-amps


41093-94

Maximum

Breaker

Duty

FP

Read

and

Write:

0

to

4.29E+09

amps


41096

Programmable Breaker Alarm #1 Mode

INT

41099

Programmable Breaker Alarm #2 Mode

INT

41102

Programmable Breaker Alarm #3 Mode

INT

Read and Write:

0

for

Disabled

1

for

Percent

duty

2 for Breaker operations

3 for Clearing time


41097-98

Programmable Breaker Alarm #1 Limit

FP

41100-01

Programmable Breaker Alarm #2 Limit

FP

41103-04

Programmable Breaker Alarm #3 Limit

FP

Read

and

Write:

If mode is 0: Reads 0, any value writes 0

If mode is 1: 0.00 to 100.00%

If mode is 2: 0 to 99,999

If mode is 3: 0, 20 to 1000 milliseconds

Relay Data Setting Parameters

41259-60

Phase

Demand

Alarm

Level

FP

41261-62

Neutral

Demand

Alarm

Level

FP

41263-64

Negative-Sequence Demand Alarm Level

FP

Read

and

Write:

0 to 16.0 amps

41265

Major

Alarm

Mask

MSBs BM(16)

41267

Minor

Alarm

Mask

MSBs BM(16)

41269

Logic

Alarm

Mask

MSBs BM(16)